• sales@alatuji.com

     

  • 021 8690 6777
    021 8690 6770
  • 0812 9595 7914 (Mr. Parmin)
    0813 1066 1358 (Ms. Eki)
    0812 8333 5497 (Mr. Muslim)
  • 0812 1248 2471 (Mr. Alfin)
    0819 4401 4959 (Mr. Arya)

Power Line and Environmental Monitor OM-PQR1010

 

- Measures All Types of Disturbances Including Spikes, Sags, Surges, Common Mode Noise, High Frequency Noise, Dropouts, Power Failures
- Datalogging - Stores Average Reading Every Minute for up to 11 Days on Each Channel
- 1500 Event Storage Per Input, 9000 Events Total for 6 Channels
- Records Magnitude, Time and Date of Each Disturbance


Feature

Electronic equipment is damaged more often by power disturbances than by fire, theft and vandalism combined. Intermittent power problems are the most expensive hidden expense to users of microprocessor-based equipment.

 

 

The OM-PQR1010 power quality recorder is a state-of-the-art, fully integrated instrument that measures, records and reports power disturbances, aiding in the analysis of power quality in medical, commercial and industrial applications.

 

 

The OM-PQR1010 monitor unit will detect a wide range of power disturbances including spikes, sags, surges, common mode noise, dropouts and high frequency noise on two phases of ac voltage and one dc voltage channel; it will also test the temperature, humidity and ac current. For ac current measurement, the OM-PQR1010 is equipped with a pair of banana jacks designed to accept a 10 mV/output current transducer (CT). Disturbances detected on multiple channels are recorded by their time, date, magnitude and duration in a non-volatile RAM memory. Stored data can then downloaded and analyzed by connecting the OM-PQR1010 to your PC’s serial port and running the included Windows data analysis software. Input connections to the OM-PQR1010 are made between the safety connectors on the back of the unit and the circuit panel to be tested. The OM-PQR1010 operates on standard 110 Vac/220 Vac power. Once plugged in, the OM-PQR1010 immediately begins testing the signals on the input connectors.


Spesification

GENERAL


Summary Event Count: 56,000 of each event type
Detail Storage: 1500 events per channel
Data Retention: 5 years without power
Datalogging Sample Rate: programmable from 1 reading per second to 1 reading per 4 minutes
Impulse Detection: 500 nanoseconds
Communications: RS-232, 1200 to 19,200 baud (programmable), 8 data bits, 1 stop bit, no parity
Input Connections: ac voltage, safety banana jacks; dc voltage, BNC; current (CT), banana jacks; temperature, phone jack; humidity, mini-DIN
Operating Temperature: 0 to 50oC (32 to 122°F), 10 to 80% RH non-condensing
 

Operating Voltage: 12 to 30 Vdc, 80 to 260 Vac
Operating Current: 0.1 A
Operating Line Frequency: dc to 400 Hz
Weight: 1.8 kg (4 lb)
Dimensions: 203 mm H x 254 mm W x 51 mm D (8 x 10 x 2")
Power Cord: 1.8 M (6')

 

 

AC/DC VOLTAGE CHANNELS DATALOGGING


Range: ac voltage, 80 to 520 Vac RMS; dc voltage, ± 1 to ± 52 Vdc
Accuracy: ± 1.5%
 

SAGS/SURGES
     Threshold: 5% and 10% of average, or user programmed levels
     Duration Limits: 1 cycle or 20 ms
     Accuracy: ± 1.5%
 

DROPOUTS
     - Threshold: ac voltage, less than 10 V RMS; dc voltage, less than 10% of  

avg
     - Duration Limits: longer than 8 ms, shorter than 80 ms
 

POWER FAILURES
     - Threshold: ac voltage, less than 10 V RMS; dc voltage, less than 10% of  

avg
     - Duration Limits: longer than 80 ms
 

IMPULSES
     - Resolution: 2 channels: 20 V to > 2500 V peak
     - Threshold: 20, 70, 140, 300, 850, 2.5 kV
     - Duration Limits: 500 nanoseconds above threshold
     - Accuracy: ± 10%
 

 

HIGH FREQUENCY NOISE
     - Range: 2 volts peak, 10 kHz to 10 MHz
     - Accuracy: ± 10%
     - Response Time: 1 ms AC VOLTAGE LINE FREQUENCY
     - Range: 40 to 400 Hz
     - Accuracy: ± 1%
     - Response Time: 1 ac cycle
     - Threshold: ± 2% deviation from average

 

HUMIDITY CHANNEL DATALOGGING
- Range: 10% to 90% RH non-condensing
- Accuracy: ± 5%
 

 

SAGS/SURGES
     - Threshold: 5% and 10% of average, or user programmed levels
     - Duration Limits: 2 seconds
     - Accuracy: ± 5%

 

CURRENT CHANNEL DATALOGGING
- Input: current transducer (CT), 10 mV/A output
- Range: 0.2 A to 1000 A RMS
- Accuracy: ± 1.5%
 

 

SAGS/SURGES
     - Threshold: 5% and 10% of average, or user programmed levels
     - Duration Limits: 20 ms
     - Accuracy: ± 1.5%
 

 

DROPOUTS
     - Threshold: less than 10% of average
     - Duration Limits: longer than 8 ms, shorter than 80 ms
 

 

POWER FAILURES
     - Threshold: less than 10% of average
     - Duration Limits: longer than 80 ms

 

 

TEMPERATURE CHANNEL DATALOGGING

- Sensor: semiconductor transistor
- Range: -7 to 121°C (20 to 250°F) (0.02 to 2.5 Vdc)
- Accuracy: ± 1%
- Sample Rate: programmable from 1 reading per second to 1 reading per 4 minutes
 

 

SAGS/SURGES
     - Threshold: 5% and 10% of average, or user programmed levels
     - Duration Limits: 2 seconds
     - Accuracy: ± 1.5%

Inquiry

Name :
Company :
Address :
Email :
Handphone :
Subject :
Product Name :
Product Type :
Message :
   

Video

Tidak ada video untuk produk ini

Testimoni

Download PDF

Tidak ada file catalog untuk produk ini


Artikel Terkait dengan Produk Power Line and Environmental Monitor OM-PQR1010


NEWSLETTER

 

TESTIMONIALS

B2TKS

B2TKS
Sangat jarang perusahaan seperti ini di Indonesia!  Mereka terus-menerus mengikuti perkembangan inovasi engineering test & measurement, “nyambung” berdiskusi teknis dan berpengalaman, memiliki visi pengembangan teknologi pengukuran, pengujian, inspeksi dan monitoring.(Dr.-Ing. Ir. May Isnan - NDT Specialist B2TKS-BPPT)

Chevron

Chevron
Tim kerja Alat Uji dapat diandalkan. Sangat bagus dalam implementasi di lapangan. Secara umum kami puas dengan services nya!(Andre - HSE Chevron)

BPPT

BPPT
Saya baru sekali ini bertemu perusahaan engineering yang eksis seperti ini di Indonesia.  Sangat terbantu dengan solusi yang diberikan, sangat memuaskan!(Muksin Saleh, ST., MT - Fuel Conversion and Pollution Control Specialist, B2TE - BPPT)

BALITBANG

BALITBANG
Sistem monitoring yang disuplai oleh Alat Uji adalah yang tertinggi ratingnya sampai dengan saat ini dibandingkan sistem lain yang pernah kami miliki, Dengan sistem monitoring dari Alat Uji, Pengujian kami jadi lebih terkontrol karena ada visualisasi di sistemnya. (Gatot Sukmara - Badan Penelitian dan Pengembangan, Departemen Pekerjaan Umum)

 
Alat Uji Alat Uji Alat Uji Alat Uji Alat Uji Alat Uji